Power Range: 45 – 294 kVA

3:3

15-240 kW + redundancy
25-400 kW + redundancy
42-1008 kW + redundancy

 

Riello UPS MULTI POWER (MPW and MPX) is a three-phase uninterruptible power supply with a modular architecture, ON LINE Double Conversion type, with the possibility of redundant.

It delivers a rated power from 15 to 1176 kW and it is manufactured using specially-designed components and transformerless technologies that deliver exceptional efficiency up to 96.5%, and high power density in a compact footprint.

Modularity reduces the risk of wasteful oversizing at installation, while offering “pay as you grow” scalability when it’s time to expand, optimising initial investment and total cost of ownership (TCO).

It is designed to protect:

  • any critical high-density computer and IT environment
  • data centers
  • critical loads

 

Models MPX 75 (MPX 130 PWC)
OVERALL SPECIFICATION
Cabinet type MPX 130 PWC Power Cabinet
Power Module nominal power (Named PM) 15 kW
Solution nominal Power 75 kW
Output power factor [pf] 1
Parallelable (up to) 4
Cabinet layout description 5 x MPX 15 PM
INPUT
Rated power 75000 VA
Voltage 380 / 400 / 415 V three-phase + N
Frequency tolerance 40 – 72 Hz
Power factor 1
BY PASS
Rated voltage 380 / 400 / 415 V three-phase + N
OUTPUT and INVERTER OUTPUT
Rated power 75000 VA
Active power 75000 W
Number phases 3
Output Voltage 380 / 400 / 415 V three-phase + N
Dynamic stability EN62040-3 class performance 1 non linear load
Frequency 50 or 60 Hz
MODULAR BATTERIES
Battery Cabinet Type Modular Type (MPW 170 BTC)
Layout Modular type made up by Battery Unit (named BU)
Battery features VRLA batteries lined up inside BU; Constant voltage and current measuring at BU level; Battery status monitoring via Multi Power LCD display
Cabinet lay out description 9 x Battery shelves
Dimensions (h w d) 2000x600x1050 mm
Weight (without PM / BU ) 280 kg
CONVENTIONAL BATTERIES
Battery Cabinet Type Conventional Type
Layout Free Standing Battery cabinet / Shelf
Battery features Conventional battery Blocks VRLA Type
Cabinet lay out description 1 x (20 + 20) Blocks
Dimensions (h w d) 2000x860x800 mm
Weight (without PM / BU ) 250 kg
ENVIRONMENTAL
Color RAL 9005
Protection rating IP20 finger proof (either with cabinet doors open or close)
Noise (at 1 m) <65 [dBA±2]
Standards European directives: L V 2014/35/EU low voltage; EMC 2014/30/EU electromagnetic compatibility — Directive & Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2 – category C2; RoHS compliant — Classification in accordance with IEC 62040-3 VFI – SS – 111
DATA
Weight 145 kg
Dimensions (h w d) 1200x600x1050 mm
Input phases 3
Output phases 3

 